Checking The Ionisation Current; Checking The Draught - Viessmann VITOGAS 100-F Service Instructions Manual

Rated heating output of 29 to 60 kw gas boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps

Checking the ionisation current

8888
D Burner control unit
1. Pull ionisation cable C from ionisa-
tion electrode E.

Checking the draught

Measure the draught behind the draught
hood in Pa (100 Pa = 1 mbar) and record
it in the service report on page 28.
12
2. Connect the measuring device A as
shown in the diagram:
■ Push plug-in adaptor (7 6/4) B
into ionisation cable C.
■ Push adaptor cable (7 4/6) F
onto ionisation electrode E.
■ Push measuring device plug A
into plug-in adaptor B and adap-
tor cable F.
3. Start the boiler.
4. Check the ionisation current.
■ When the pilot burner is lit:
Min. 1.0 µA
■ When the main burner is lit:
Min. 3.0 µA
5. Record the actual values in the report
on page 28.
Note
Required boiler draught: 3 Pa
(0.03 mbar).
The chimney draught must not exceed
10 Pa (0.1 mbar). It may be necessary to
fit a draught stabiliser into the chimney.
(Seek the agreement of your local flue
gas inspector [where appropriate].)
(cont.)