Commissioning/service reports

Commissioning/service reports
Settings and actual val-
ues
Static pressure
Supply pressure (flow
pressure)
= for natural gas E
= for LPG
Tick gas type
Nozzle pressure
Carbon dioxide content
CO
2
Oxygen content O
Carbon monoxide con-
tent CO
Flue gas temperature
(gross)
Flue gas loss
Ionisation current
Draught
28
Date
By
mbar
mbar
mbar
mbar
% by vol.
% by vol.
2
ppm
°C
%
µA
Pa
Set value
Commis-
sioning
Max.
57.5 mbar
8-25 mbar
27.7-57.5
mbar
Min. 3 µA
Max. 10 Pa
(0.1 mbar)
Min. 3 Pa
(0.03 mbar)
Mainte-
nance/Serv-
ice