Lennox CLIMATIC 50 User Manual page 87

Hide thumbs Also See for CLIMATIC 50:
Table of Contents

Advertisement

Type Index
Name NV
INT
1
I_Sp_BMS_Dog
INT
1
O_Sp_BMS_Dog
INT
2
I_Sp_RunUnit_BMS
INT
2
O_Sp_RunUnit_BMS
INT
3
I_Sp_ChOver_BMS
INT
3
O_Sp_ChOver_BMS
INT
4
I_Sp_Rotat_BMS
INT
4
O_Sp_Rotat_BMS
INT
17
O_Error_Codes
INT
18
O_R_FCoil_PWM_1
INT
19
O_R_FCoil_PWM_2
INT
20
O_R_FCoil_PWM_3
INT
21
O_R_FCoil_PWM_4
INT
22
O_Error_Bits_1
INT
23
O_Error_Bits_2
CLIMATIC 50, user manual – Chillers ranges
Type NV Direction Index
8
input
208
8
output
208
8
input
209
8
output
209
8
input
210
8
output
210
8
input
211
8
output
211
8
output
224
81
output
225
81
output
226
81
output
227
81
output
228
8
output
229
8
output
230
[ BMS ] Activation of the control by a
computer or an automat - mode BMS is
activated if this value is different from
zero, This value is decreased every
second
[Unit] without pump: 0=Started;
1=Stopped
[Unit] with pump: 1=Stopped; 2:P1 Only;
3=P2 Only; 4=P1-N P2-S; 5=P2-N P1-S;
6=P1/P2 by clock
[Unit] Change-over: 0=Cool. Only;
1=Heat. Only; 2=Auto. Pump; 3=Auto.
No Pump
[Unit] Activation of the circuits: (WA)
0=C1 Only; 1=C2 Only; 2=C1/C2 by
clock
(LC) bit.0=C1; bit.1=C2; bit.2=C3;
bit.3=C4
[Alarm] Code Error
[% of opening] Fan, Modulation,
Circuit 1
[% of opening] Fan, Modulation,
Circuit 2
[% of opening] Fan, Modulation,
Circuit 3
[% of opening] Fan, Modulation,
Circuit 4
[Alarm]
bit.0 = Flow switch
bit.1 = High Temperature, Outlet
bit.2 = Low Temperature, Inlet
bit.3 = Low Temperature, Outlet
bit.4 = High Temperature, Intlet
bit.5 = Pump, 1
bit.6 = Pump, 2
bit.7 = Real Time Clock
bit.8 = BE50
bit.9 = BM50, Slave
bit.10 = Probes & Sensors
bit.11 = Condenser
bit.12 = Fans, Condenser, Circuit 1
bit.13 = Fans, Condenser, Circuit 2
bit.14 = Fans, Condenser, Circuit 3
bit.15 = Fans, Condenser, Circuit 4
[Alarm]
bit.0 = Compressor, Circuit 1, Electric
Protection
bit.1 = Compressor, Circuit 1, High
Pressure
bit.2 = Compressor, Circuit 1, Low
Pressure or Freeze protection
bit.3 = Compressor, Circuit 2, Electric
Protection
bit.4 = Compressor, Circuit 2, High
Pressure
bit.5 = Compressor, Circuit 2, Low
Pressure or Freeze protection
bit.6 = Compressor, Circuit 3, Electric
Protection
bit.7 = Compressor, Circuit 3, High
Pressure
CL50-CHILLERS/IOM/0906-E
WA LC
DS50
3934
3112
(BMS)
3311
BMS
3411
(BMS)
1000
2619
2629
2639
2649
85
85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents