Midea MFGA-60ARDN1-QC2 Service Manual page 29

Floor standing type
Table of Contents

Advertisement

Electronic scale
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way
valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at
the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to
ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set
to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid
refrigerant.
If the system cannot be charge with the specified amount of refrigerant, or can be charged
with a little at a time (approximately 150g each time) , operating the air conditioner in the
26