Midea MFGA-60ARDN1-QC2 Service Manual page 20

Floor standing type
Table of Contents

Advertisement

Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3). Air purging
Open the valves on the charging cylinder and the charge set. Purge the air by loosening
the flare nut on the 2-way valve approximately 45' for 3 seconds then closing it for 1
minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant
Close the valve on the charging cylinder and discharge the refrigerant by loosening the
flare nut on the 2-way valve approximately 45' until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way
valves to the open position.
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N·m.
Be sure to check the gas leakage.
3. Adding the refrigerant if the pipe length >5m
17