The following steps and diagram indicate the location of the
connection points required to measure the manifold pressure.
The manifold pressure may be measured using a U-Tube Manometer
or a Differential Pressure Gauge. The diagram shows the connection
of both measuring devices. Only ONE DEVICE IS REQUIRED to
measure the manifold pressure.
Remove the plug. Install the appropriate barbed fitting and connect
the pressure side line from the U-Tube Manometer or Differential
Pressure Gauge.
figure 17 - manifold pressure measurement detail
figure 18 - gas Valve
PRESSURE REGULATOR
ADJUSTMENT (UNDER CAP SCREW)
INLET
PRESSURE
TAP
INLET
GAS CONTROL KNOB
CHeCk ouT proCedure and adjusTmenT
WIRING TERMINALS (2)
VR8205
ON
OFF
Refer to "CHECK OUT PROCEDURE AND ADJUSTMENTS" in
this manual when reading the manifold pressure.
When measurement is completed, disconnect the U-Tube
Manometer or Differential Pressure Gauge. Be sure to reinstall the
⅛" plug, using appropriate pipe thread sealant approved for use with
natural and liquefied Petroleum gases.
OUTLET
PRESSURE
TAP
Regulator cover screw must be installed at
all times unless adjusting manifold pressure.
Firing rate and manifold pressure must only
OUTLET
be measured with cover screw firmly installed.