11.5 Outdoor Temperature Sensor
(Optional)
Outdoor Temperature Sensor Installation
1. Pull out the sensor body from the cap.
2. Attach the body to the wall using the screws/anchors provided
with the device.
3. Run the wires into the device body through the grommet
opening.
4. Connect the wires to the terminal block.
5. Attach the cap to the body.
Navien Outdoor Temperature Sensor Kit
Outdoor Temperature Sensor Installation Guidelines
Avoid areas with temperature fluctuations by direct sunlight,
and where the temperature may not be representative of true
outdoor temperature.
Best location to install the temperature sensor is on a North or
Northeast side of a structure under eaves where the sensor is
shielded from direct sunlight.
Avoid placing sensor in close proximity of heat sources that may
affect correct temperature sensing. (fans, exhausts, vents, lights)
Avoid installing the sensor in areas where the sensor is subjected
to excessive moisture.
Use 18 gauge wiring (thermostat wiring) with no splices. (except
at the unit harness connection with yellow leader wire.)
Caution should be taken to avoid potential electromagnetic
interference (EMI) by routing separately from potential sources
such as line voltage wiring. When necessary, shielded cable may
be used.
Make sure wiring connections are secure before closing the cap.
The sensor is a water resistant device.
Any damage to the device may require the replacement of the
entire component.
Appendixes
80
11.6 Outdoor Reset Control (Available with
Optional Outdoor Temperature Sensor)
The Outdoor Reset Control feature may be used to enhance energy
efficiency while maintaining optimal heating performance. With
the Outdoor Reset Control, the space heating temperature setting
automatically changes according to the outdoor temperature and
the current space heating system application (system load).
You can configure the Outdoor Reset Control settings on the front
panel by entering the Special Parameter Setting mode. Refer to
"10.5 Setting the Parameters" on page 56.
The Outdoor Reset Control feature requires
Note
installation of an outdoor temperature sensor, and it
only works when the boiler is running in the normal
operation mode. It does not work when the boiler is
running in either the Minimum (MIN) or Maximum
(MAX) mode, or when the boiler's front panel displays
a fault.
Outdoor
High MIN
Absolute
MAX
Absolute
MIN
°F
113 104 95 86
77 68
59 50
41
°C
45 40
35 30
25 20
15 10
5
Space Heating Temperature Setting for the
Outdoor Reset Control Feature
The following tables list the default space heating temperature
range by system heat load and the applicable outdoor
temperature ranges.
Outdoor
Low MIN
°F °C
194
90
185
85
176
80
167
75
High Mass Radiant
158
70
Low Mass Radiant
149
65
140
60
Cast Iron Baseboard
131
55
Custom
122
50
Radiator
113
45
104
40
Finned Tube Baseboard
95
35
Fan Coil
86
30
77
25
68
20
59
15
50
10
32 23 14
5
-4 -13
0
-5 -10 -15 -20 -25