6.2 Selecting Vent Pipe Materials

Venting requirements differ in the US and Canada. Consult the
following chart or the most recent edition of ANSI Z223.1/NFPA
54 or CAN/CGA B149.1, as well as all applicable local codes and
regulations when selecting vent pipe materials. Do not use cellular
core based pipe materials for the exhaust vent.
Locale
Recommended Vent Materials
PVC Schedule 40 (Solid Core)
CPVC Schedule 40 or 80 (Solid Core)
USA
Approved Polypropylene*
Type BH Special Gas Vent Class IIA (PVC)
Type BH Special Gas Vent Class IIB (CPVC)
Canada**
Type BH Special Gas Vent Class IIC
(Polypropylene)
* Approved polypropylene systems include:
Duravent Polypro (Single Wall): 2PPS-xxx (2"), 3PPS-xxx (3")
Centrotherm InnoFlue SW: ISxx02xx (2"), ISxx03xx (3")
Refer to manufacturer's literature for detailed information.
For 3" venting, use the following polypropylene parts:
Duravent
2PPS-X3L (2"-3" Increaser)
Centrotherm
ISEI0203 or ISIA0203 (2"/3" Increaser)
** For installation in Canada, field-supplied plastic vent piping must comply
with CAN/CGA B149.1 (latest edition) and be certified to the Standard
For Type BH Gas Venting Systems, ULC-S636. Components of this listed
system must not be interchanged with other vent systems or unlisted
pipes or fittings. All plastic components and specified primers and glues
of the certified vent system must be from a single system manufacturer
and must not be intermixed with another system manufacturer's parts.
The supplied vent connector and vent termination are certified as part
of the boiler.
44
Venting the Boiler
CAUTION
This boiler has a built-in control to limit the exhaust
temperature to 149°F (65°C). As a result, the boiler can be
vented with Schedule 40 PVC.
In high temperature applications, the exhaust temperature
can exceed 149°F (65°C). In that case, you must use Schedule
40 or 80 CPVC or Approved Polypropylene in the USA
or Type BH Special Gas Vent Class IIB (CPVC) or Class IC
(Polypropylene) that conforms to ULC-S636 in Canada.
In systems with 2 in. vents, if the exhaust temperature
exceeds 149°F (65°C), CPVC pipe (field supplied) must
be used for the first 3 feet of equivalent pipe length. For
systems with 3 in. vents, if the exhaust temperature exceeds
149°F (65°C), CPVC pipe (field supplied) must be used for the
first 5 in. of equivalent pipe length.
If you require that return water hotter than 140°F (60°C) to circulate
back to boiler, the DIP switch must be configured (Dip Switch 2,
switch #8 to ON position). Otherwise, the boiler will control and
maintain the flue and DHW temperature below 150°F (65°C) and
140°F (60°C) respectively.
When PCB DIP switch 2 #8 is set to Off (factory
Note
default), the boiler does not operate without an
exhaust thermostat installed.
When you set PCB DIP switch 2 #8 to On, ensure
that CPVC piping is used for exhaust venting.