History; History Data Mode - Honeywell KS20S KaltecSoft Evolution Operation Manual

Hide thumbs Also See for KS20S KaltecSoft Evolution:
Table of Contents

Advertisement

Available languages

Available languages

8.6.4. Operation cycles
First cycle
The display shows set CYCLE 1 and the cycle type flashes.


Push
to scroll through the cylces.
WS1CI Only Upflow Regenerant Refill After Rinse
• 1st cycle: Fill
• 2nd cycle: Softening
• 3rd cycle: Draw up
• 4th cycle: Backwash
• 5th cycle: Rinse
• 6th cycle: End
Caution! Do not change the operation cycles or their
order. Any changes of the operation cycles will prevent
the device from functioning correctly.
Caution! Do not change the control valves from down-
flow to upflow brining or vice versa.
The valve bodies for downflow and upflow are unique
to the regeneration type and should not be interch-
anged. A mismatch of valve body and regeneration
piston will result in hard water bypass during service.
Last cycle
Push
to go to the last cylce.
The display shows END.
Setting the contact data of the installer
1. Push
and
to set the contact data of the installer.



2. Push
or
telephone number of the installer.
3. Push
to go to the next digit.
Note! Maximum number of digits to set is eleven.
4. Push
to set the name of the installer.
5. Push
or
name of the installer.
6. Push
to go to the next letter.
Note! Maximum number of digits to set is eighteen.
7. Push
to exit the settings.
The display shows TIME OF DAY or another general para-
meter (see 8.1. General parameters).
MU5H-1419GE23 R0815
for 3 seconds to enter the level
to change the first digit of the
to change the first letter of the
Note! Remember to lock the set mode after the setting
of the parameters.
To lock the set mode please see 8.5.2. Locking the set mode.

9. History

The KS20S softener saves the follwing parameters in cont-
roller history:
• Number of days since the last regeneration
• Salt consumtion since the last regenetation
• Salt consumption since start-up
• Total number of regenerations since start-up
• Reserve history
• Usage history
• Maximum flow rate in the last 7 days

9.1. History data mode

Push and hold for 3 secondes both buttons
until the display shows DAYS SINCE REGEN, the
number of days since the last regeneration.
9.1.1. Consumption - last regeneration
Push
to go to the next parameter.
The display shows SINCE LAST REGEN, the consumption in
m³ since last regeneration.
Push
to go to the next parameter.
9.1.2. Usage history
The display shows USAGE HISTORY.
1. Push
or
certain day. You can choose between day 1 and 63.
Day 1
Yesterday
Day 2
The day before yesterday
:
:
Day 63
63 days before
2. Push
to go to the next parameter.
15
and
to show the usage history on a
Honeywell GmbH

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents