Water Tank Refill
1. Open the cold water supply to the tank.
2. Open a hot water faucet to vent air from the system until
water flows from the faucet, then close.
3. Depress the hot water tank pressure relief valve handle to
ensure there is no air remaining in the tank.
4. Carefully inspect all plumbing for water leaks. Correct as
required.
5. Purge all air from HRP by depressing the Schrader valve on
the HR unit. Allow all air to bleed out until water appears at
the valve.
6. Before restoring the power or fuel supply to the water
heater, adjust the temperature setting on the tank thermo-
stat(s) to ensure maximum utilization of heat available from
the refrigeration system and to conserve the most energy.
On tanks with thermostats and both upper and lower ele-
ments, the lower element should be turned down to 100_F,
while the upper element should be adjusted to 120_F. De-
pending upon the specific needs of the customer, you may
need to adjust the upper element differently.
On tanks with a single thermostat, lower the thermostat set-
ting to 120_F or the "LOW" position. After thermostat ad-
justments are completed, replace access cover and restore
electrical or fuel supply to water heater.
IMPORTANT: Copper should be used for piping from HRP to
domestic water tank(s).
Use 5/8" (16mm) O.D. copper or
larger. Refer to local codes for hot water piping. Insulate the
water lines between the GHP and the water heater with a
minimum of 3/8" (10mm) closed cell insulation.
Heater
Model
208V
KWAEH0101N10
7.2
KWAEH0101F15
10.8
KWAEH0101F20
14.4
X = Compatible
Table 3 – Electric Heater Compatibility
kW
Stages
230V
208V
9.6
2
24600
14.4
2
36900
19.2
2
49200
Initial Start- -Up
!
UNIT DAMAGE AND/OR OPERATION HAZARD
Failure to follow this caution may result in unit damage
and/or improper equipment operation.
Make sure all valves in heat recovery water piping system
are open. NEVER OPERATE HR PUMP DRY.
1. Turn on the heat pump. The HR pump should not run if the
compressor is not running.
2. Turn HR switch to the "ON" position. The pump will oper-
ate if entering water temperature to HR is below 120_F.
3. The temperature difference between the water entering and
leaving the heat recovery should be 5_F to 15_F.
4. Allow the unit to operate for 20 to 30 minutes to ensure it is
functioning properly. The pump should shut off when the
water temperature entering the heat recovery reaches 120_F.

FIELD INSTALLED ACCESSORIES

Auxiliary Heaters
Internally mounted auxiliary heaters are available in 10 Kw, 15 Kw
and 10 Kw sizes.
instructions shipped with the heaters. Table 3 lists compatible
heaters with GT units.
Flow Centers and Associated Loop Accessories
A wide variety of flow centers are available for both closed and
open loop installations, along with hose kits, fittings, solenoid
valves, etc.
Refer to the instructions shipped with these
components for further details.
Btu/h
230V
GT024
32700
X
49100
63400
20
CAUTION