4-4
Composition of Main Circuit Terminals
400V systems
Model
SVC06-0007-4
SVC06-0015-4
SVC06-0022-4
SVC06-0040-4
SVC06-0055-4
SVC06-0075-4
SVC06-0110-4
SVC06-0150-4
*1 In this example, the maximum
As shown in the example, to protect the brake resistor, F1115 (Duty cycle of brake resistor) shall be set at 10% ED
or less. When % ED needs to be set above 10 %, brake resistor capacity should be increased proportionally.
Example) When setting 20 % ED, the capacity should be doubled.
External brake resistor (recommended)
Resistance
Capacity *1
700Ω or more
320Ω or more
160Ω or more
120Ω or more
80Ω or more
60Ω or more
40Ω or more
40Ω or more
duty cycle
of the brake resistor is assumed to be 10% ED.
- 28 -
External brake resistor (limit value)
Resistance
380Ω or more
100W
190Ω or more
200W
130Ω or more
400W
80Ω or more
600W
52Ω or more
800W
38Ω or more
1000W
32Ω or more
1500W
32Ω or more
1500W
Capacity *1
150W
300W
500W
800W
1100W
1500W
1800W
1800W