Chapter 5
ETH-1000 Configuration
The steps to configure the ETH-1000 module to work with the ControlLogix PLC using EtherNet/IP Implicit
Messaging and Mitsubishi controllers using MC Protocol are documented.
Configuring the Validation System as shown in Figure 2 is used as the example. Some parameters will need
different values to properly reflect the actual system a user is configuring. However, the example configuration
can be used to simplify the overall configuration effort.
The user should have gone through the configuration steps as shown in Section 3.2 of this document.

5.1 Configuring the EtherNet/IP Implicit Messaging Communication

1. Select the "Ethernet Multiple" Protocol Selection box and check "EtherNet/IP Server" and "MELSEC
Client" selections. Selecting these two check boxes allow the EtherNet/IP and MELSEC tabs to
become active. The screen also shows the current IP Address of the ICC Module and the
Authentication User Name and Password if they are needed.