Advertisement

C2648 Prodigy and Prodigy Plus Service Manual

Pressure switch

High pressure cut out. The high pressure cut out switch will open at a preset pressure, shutting off power to
the compressor contactor. After the pressure has fallen to another preset level, the switch will re-close and the
contactor coil will be energized.
To Test High Pressure Switch:
A. Attach refrigeration gauge set to high side port.
B. Disconnect leads to fan motor.
C. Measure voltage at high pressure control.
D. Switch ice machine on, observe pressure that the pressure control opens at, compare to spec. Allow system
to equalize, observe the pressure that the pressure control closes at, compare to spec.
Transformer
Check secondary voltage, it must be between 10 and 15.5 AC volts. Replace if no voltage is output or if above
or below the acceptable voltage..
Controller
The controller's software operation is confirmed if it is functioning. Execute the test to confirm its operation of
the loads. Illumination of a diagnostic code (other than E) is not an indication of controller failure. Each code
requires its own diagnosis.