Gree GWC09QB-K3DNA1B Service Manual page 47

Hide thumbs Also See for GWC09QB-K3DNA1B:

Advertisement

Turn on the unit
and wait 1 minute
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
Voltage higher than 200V?
N
Measure the AC voltage between
terminal L and N on wiring board
XT(power supply)
Voltage within
210VAC~250VAC?
Y
Shut down the power and wait 20 minutes;
or use DC voltmeter to measure the voltage
on the two ends of capacitor , until the
voltage is lower than 20V
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
If the wiring of
reactor L is normal?
Y
Replace the control
panel AP1
End
Fault with the voltage
testing circuit on
Y
control panel AP1
Shut down the power
and repair the power
N
supply to restore the
range
210VAC~250VAC
Connect the reactor
Laccording to Elec-
Re-energize and
N
trical Wiring Diagr-
turn on the unit
am correctly
Replace the control
panel AP1
power on and
If the fault is
restart the unit
eliminated?
N
If the fault is
eliminated?
N
Y
Y