Field Settings; Procedure; Detailed Description - Daikin EKHBH008BB3V3 Operation Manual

Indoor unit and options for air to water heat pump system
Hide thumbs Also See for EKHBH008BB3V3:
Table of Contents

Advertisement

5.
F
IELD SETTINGS
NOTICE
The default values mentioned in
page 18
are the values from factory. The actual initial
values shall be selected according to your application.
These values shall be confirmed by your installer.
CAUTION
The field settings [2] depends on the applicable
legislation.
The field settings [9] depends on the application.
Before changing these settings, the new values shall
be confirmed by the installer and/or shall be according
to the applicable legislation.
The indoor unit shall be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user demand. However, the field settings mentioned in
table" on page 18
can be modified to customer preferences. Thereto,
a number of so called field settings are available. These field settings
are accessible and programmable through the user interface on the
indoor unit.
Each field setting is assigned a 3-digit number or code, for example
[1-03], which is indicated on the user interface display. The first digit
[1] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under
settings table" on page
18. In this same list, we provided for 2
columns to register the date and value of altered field settings at
variance with the default value.
A detailed description of each field setting is given under
description" on page
13.

5.1. Procedure

To change one or more field settings, proceed as follows.
3
2
1
Press the
button for a minimum of 5 seconds to enter FIELD
SET MODE.
The
icon (3) will be displayed. The current selected field
setting code is indicated
the right
(1).
2
Press the
button to select the appropriate field setting
first code.
3
Press the
button to select the appropriate field setting
second code.
4
Press the
button and
the set value of the select field setting.
Operation manual
13
"Field settings table" on

"Field settings

"Field
"Detailed
(2), with the set value displayed to
button to change
5
Save the new value by pressing the
6
Repeat step 2 through 4 to change other field settings as
required.
7
When finished, press the
NOTICE
Changes made to a specific field setting are only stored
when the
setting code or pressing the
change made.
INFORMATION
Before shipping, the set values have been set as
shown under
When exiting FIELD SET MODE, "88" may be
displayed on the user interface LCD while the unit
initialises itself.

Detailed description

[0] User permission level
If required, certain user interface buttons can be made unavailable for
the user.
Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons
simultaneously pressing buttons
buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
by the field setting [0-00].
Button
Quiet mode button
Weather dependent
set point button
Schedule timer enable/
disable button
Programming button
Time adjust buttons
Inspection/test
operation button
1
Indoor unit and options for air to water heat pump system
button.
button to exit FIELD SET MODE.
button is pressed. Navigating to a new field
button will discard the
"Field settings table" on page
and
immediately followed by
and
, and keeping all 4
Permission level
1
2
operable
operable
operable
operable
operable
operable
operable
4PW62571-1A – 05.2011