TABLE 3.5 Recommended cable size and torque requirements

kVA
Input
Output
Capacity
Voltage
Voltage
30kVA
480V
480V
480V
208V
50kVA
480V
480V
480V
208V
80kVA
480V
480V
480V
208V
*1 – The cables must be selected to be equal to or larger than the sizes listed in the table.
*2 - Voltage drop across power cables not to exceed 2% of nominal source voltage -
*3 - Allowable ampere rating based on 75 C insulation at ambient temperature of 40 C
No more than 3 conductors in a raceway without de-rating.
Note : Copper conductors are assumed.
2033D SERIES UPS
OWNERS / TECHNICAL MANUAL
Input Side * 1, 2
Cable
Torque
Size
in. lbs
6 AWG
42-56
or larger
in. lbs
6 AWG
42-56
or larger
in. lbs
3 AWG
200 - 269
or larger
in. lbs
3 AWG
200 - 269
3/0 AWG
or larger
in. lbs
1/0 AWG
200-269
1/0 AWG
or larger
in. lbs
1/0 AWG
200-269
2x2/0 AWG
or larger
in. lbs
MITSUBISHI ELECTRIC 2033D SERIES UPS
Output Side * 1, 2
Cable
Torque
Size
in. lbs
6 AWG
42-56
or larger
in. lbs
or larger
1 AWG
200-269
or larger
in. lbs
or larger
4 AWG
100-135
or larger
in. lbs
or larger
347-469
or larger
in. lbs
or larger
200-269
1/0 AWG
or larger
in. lbs
or larger
347 - 469
1/0 AWG
or larger
in. lbs
or larger
Page Number:
Bypass Side * 1, 2
Cable
Torque
Size
in. lbs
6 AWG
42-56
4 AWG
in. lbs
or larger
6 AWG
42-56
4 AWG
in. lbs
or larger
3 AWG
200 - 269
1 AWG
in. lbs
or larger
3 AWG
200 - 269
1 AWG
in. lbs
or larger
200-269
4/0 AWG
in. lbs
or larger
200-269
4/0 AWG
in. lbs
or larger
3-5
DC Input Side * 1, 2
Cable
Torque
Size
in. lbs
100-135
in. lbs
100-135
in. lbs
200-269
in. lbs
200-269
in. lbs
347-469
in. lbs
347-469
in. lbs