This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass
circuit. Bypass input circuit breaker (MCCB) are to be field supplied and installed.
Recommended Breaker (MCCB)'s Specifications are as follows:
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)
30
50
80
AC input and AC output over current protection and disconnect devices shall be field
supplied and installed. DC output over current protection and disconnect device shall
be field supplied and installed. The over current protection device shall be rated as
indicated in TABLE 1.4.
2033D SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 2
480
480
480
MITSUBISHI ELECTRIC 2033D SERIES UPS
Page Number:
Recommended
Breaker (Aac)
36
45
60
80
96
125
1-2