Table 3.4 Recommended Cable Sizes; Table 3.5 Recommended Hardware - Mitsubishi Electric 9900B Series Owner Technical Manual

Uninterruptible power supply system
Table of Contents

Advertisement

kVA
Input
Output
Capacity
Voltage
Voltage
300kVA
480V
480V
500kVA
480V
480V
750kVA
480V
480V
*1 – Use 75 degree C copper wire.
*2 - The cables must be selected to be equal or larger to the sizes listed in the table.
*3 - Voltage drop across power cables not to exceed 2% of nominal source voltage.
*4 - Allowable ampere-capacities based on copper conductors with 75 degree C. insulation at ambient temperature of 40 degree C.
▲ For other stored energy systems, refer to the attached supplement.
Table 3.5
Recommended Hardware
UPS Capacity
Bolt size
300kVA
M12 x 40mm
500kVA
M12 x 40mm
750kVA
M12 x 40mm
MITSUBISHI
ELECTRIC
OWNERS / TECHNICAL MANUAL

Table 3.4 Recommended Cable Sizes

Input Side
Cable
Torque
Size
in. lbs
3 x 1/0
347 - 469
3 x 1/0
or larger
in. lbs
or larger
3 x 250MCM
347 - 469
3 x 250MCM
or larger
in. lbs
or larger
3 x 600MCM
347 - 469
3 x 600MCM
or larger
in. lbs
or larger
Split
Flat washer
lockwasher
size
size
M12
M12
M12
M12
M12
M12
MITSUBISHI ELECTRIC 9900B SERIES UPS
9900B SERIES UPS
*1, *2, *3, *4, ▲
Output Side
Cable
Torque
Cable
Size
in. lbs
Size
347 - 469
3 x 1/0
in. lbs
or larger
347 - 469
3 x 250MCM
in. lbs
or larger
347 - 469
3 x 600MCM
in. lbs
or larger
Nut size
M12
M12
M12
Page Number:
3-5
Bypass Side
DC Input Side
Torque
Cable
in. lbs
Size
347 - 469
3 x 300MCM
in. lbs
347 - 469
4 x 400MCM
in. lbs
347 - 469
5 x 700MCM
in. lbs
Torque
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs