Capacity Tables

5. Capacity Tables
5.1 Cooling Capacity
KV24CC-ARF21
Cooling
Indoor Conditions
21/15ºC DB/WB
24/17ºC DB/WB
27/19ºC DB/WB
32/23ºC DB/WB
Notes:
TC : Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input power; kW
(kW)
21ºC
TC
7.52
SC
5.56
Input
2.10
TC
7.74
SC
5.80
Input
2.23
TC
7.88
SC
5.83
Input
2.28
TC
8.03
SC
6.83
Input
2.38
Outdoor conditions (DB)
28ºC
35ºC
7.15
6.79
5.51
5.43
2.28
2.38
7.37
7.01
5.75
5.68
2.38
2.49
7.30
7.52
5.79
5.69
2.54
2.41
7.74
7.59
6.73
6.68
2.49
2.66
43ºC
6.50
5.46
2.46
6.57
5.52
2.61
6.79
5.57
2.66
7.01
6.52
2.76
14