Fer Falcon 47-26701 Installation, Servicing And User Instructions Manual page 19

Copper wall-mounted combination, gasa fired boiler for central heating, and domestic hot water production
Table of Contents

Advertisement

For further accessories please refer to:
"Flue system manual for room sealed boiler"
Example of calculation for wall inlet/outlet
with 2 pipe system
maximum total flue length: 48 metres
12 m
7
6
4
Fig. 20
3.04.3 Example of other installation with two pipe systems
Example of wall inlet/outlet
2 pipe application
Fig. 21
FALCON
12 m
5 1
2
Example of direct roof flue outlet
Fig. 22
Attention: flow resistance (reduction) equivalent in-
cluded between 38 and 48 (see table on page 14)
Remove the flue diaphragm.
The flue and air pipes must have an inclination
downward equal to 3% from boiler to outside.
°
REF.
N
DESCRIPTION
OF PIECES
3
1
1
Air bend 80 mm R/D = 0,75
2
13
Horizontal air pipe
3
1
Air wall terminal
4
1
Air inlet closing flange
5
1
Flue bend 80 mm R/D = 0,75
6
12
Horizontal flue
7
1
Air wall terminal outlet flue
TOTAL
and wall air inlet
INDUSTRIE
LENGTH OR
REDUCTION
1,5 m
13,0 m
2,0 m
2,5 m
24,0 m
5,0 m
48,0 m
Example of roof
inlet/outlet
Fig. 23
19