Toshiba RAV-SM454MUT-E Installation Manual page 23

Hide thumbs Also See for RAV-SM454MUT-E:
Table of Contents

Advertisement

Compact 4-way Cassette Type
Wired
Wireless remote controller
remote
Sensor block display of
controller
receiving unit
display
Main defective parts
Operation Timer
Ready
Indication
Flashing
GR GR OR
Outdoor unit P.C.
F31
SIM
board
Outdoor unit
H01
compressor
breakdown
Outdoor unit
H02
compressor lock
Outdoor unit current
H03
detect circuit error
Case thermostat
H04
operation
Outdoor unit low-
H06
pressure system error
Duplicated header
L03
SIM
indoor units
Group line in
L07
SIM
individual indoor unit
Indoor group address
L08
SIM
not set
Indoor unit capacity
L09
SIM
not set
Outdoor unit P.C.
L10
SIM
board
LAN communication
L20
SIM
error
Other outdoor unit
L29
SIM
error
Abnormal external
L30
SIM
input into indoor unit
(interlock)
Phase sequence
L31
SIM
error, etc.
P01
ALT
Indoor unit fan error
Outdoor unit
P03
ALT
discharge temp. error Outdoor
Outdoor unit high-
P04
ALT
pressure system error Outdoor
P05
ALT
Open phase detected Outdoor
P07
ALT
Heat sink overheat
Indoor unit water
P10
ALT
overflow detected
The fan error of the
P12
ALT
indoor unit
43-EN
Installation Manual
Judging
Parts to be checked / error description
device
Outdoor P.C. board ---- In the case of EEPROM error. Entire
Outdoor
Current detect circuit, power voltage --- Minimum
frequency was reached in the current releasing
Outdoor
control or short-circuit current (Idc) after direct
excitation was detected
Compressor circuit --- Compressor lock was detected. Entire
Outdoor
Current detect circuit, outdoor unit P.C. board ---
Outdoor
Abnormal current was detected in AC-CT or a phase
loss was detected.
Outdoor
Malfunction of the case thermostat
Current, high-pressure switch circuit, outdoor P.C.
Outdoor
board --- Pressure sensor error was detected or low-
pressure protective operation was activated.
Indoor address setting error --- There are two or more
Indoor
header units in the group.
Indoor address setting error --- There is at least one
Indoor
group-connected indoor unit among individual indoor
units.
Indoor address setting error --- Indoor address group
Indoor
has not been set.
Indoor
Indoor unit capacity has not been set.
In the case of outdoor P.C. board jumper wire (for
Outdoor
service) setting error
Network
Address setting, central control remote controller,
adapter
network adapter --- Duplication of address in central
central
control communication
control
Other outdoor unit error
1) Communication error between IPDU MCU and
Outdoor
CDB MCU
2) Abnormal temperature was detected by the heat
sink temp. sensor in IGBT.
External devices, outdoor unit P.C. board ---
Indoor
Abnormal stop due to incorrect external input into
CN80
Power supply phase sequence, outdoor unit P.C.
Outdoor
board --- Abnormal phase sequence of the 3-phase
power supply
Indoor fan motor, indoor P.C. board --- Indoor AC fan
Indoor
error (fan motor thermal relay activated) was detected.
An error was detected in the discharge temp.
releasing control.
High-pressure switch --- The IOL was activated or an
error was detected in the high-pressure releasing
control using the TE.
The power wire may be connected incorrectly. Check
open phase and voltages of the power supply.
Abnormal temperature was detected by the temp.
Outdoor
sensor of the IGBT heat sink.
Drain pipe, clogging of drainage, float switch circuit,
Indoor
indoor P.C. board --- Drainage is out of order or the
float switch was activated.
Abnormal operation of the indoor fan motor, indoor
Indoor
P.C. board, or indoor DC fan (over current or lock,
etc.) is detected.
Compact 4-way Cassette Type
Wired
Wireless remote controller
remote
Sensor block display of
controller
Air
receiving unit
display
conditioner
status
Operation Timer
Ready
Indication
Flashing
GR GR OR
P15
ALT
stop
Entire
P19
ALT
stop
P20
ALT
stop
P22
ALT
Entire
stop
Entire
P26
ALT
stop
Entire
P29
ALT
stop
Entire
P31
ALT
stop
Entire
stop
: Lighting
: Flashing
: OFF
ALT: When two LEDs are flashing, they flash alternately. SIM: When two LEDs are flashing, they flash in synchronization.
Entire
stop
Receiving unit display OR: Orange GR: Green
Entire
stop
Entire
stop
Auto-
reset
Entire
stop
Entire
stop
Entire
stop
Operation
continued
(thermost
at OFF)
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
– 22 –
Judging
Main defective parts
Parts to be checked / error description
device
Gas leakage
There may be gas leakage from the pipe or
Outdoor
detected
connecting part. Check for gas leakage.
4-way valve, indoor temp. sensors (TC/TCJ) --- An
Outdoor
4-way valve error
error was detected due to temperature drop of the
(Indoor)
indoor unit heat exchanger sensor when heating.
High-pressure
Outdoor
High-pressure protection
protective operation
Outdoor unit fan motor, outdoor unit P.C. board --- An
Outdoor unit fan error Outdoor
error (overcurrent, locking, etc.) was detected in the
outdoor unit fan drive circuit.
IGBT, outdoor unit P.C. board, inverter wiring,
Outdoor unit inverter
Outdoor
compressor --- Short-circuit protection for compressor
Idc activated
drive circuit devices (G-Tr/IGBT) was activated.
Outdoor unit position
Outdoor unit P.C. board, high-pressure switch ---
Outdoor
error
Compressor motor position error was detected.
Another indoor unit in the group is raising an alarm.
Other indoor unit
Indoor
error
E03/L07/L03/L08 alarm check locations and error
description
: The air conditioner automatically enters the auto-address setting mode.
Installation Manual
Air
conditioner
status
Entire
stop
Auto-
reset
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Auto-
reset
EN
44-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm404mut-eRav-sm564mut-e

Table of Contents