LP916A-C PNEUMATIC REMOTE BULB THERMOSTATS
CAUTION
Be careful not to change position of control shaft
when removing shipping stop and attaching setpoint
knob and scale plate to Thermostat.
Assemble Thermostat, mounting bracket, and scale
plate as shown in Figure 17.
Place setpoint knob on control shaft (Fig. 17) with
pointer aligned over mid-mark on scale plate.
Secure knob firmly with setscrew furnished to maintain
calibration.
Hold Thermostat in place in the terminal unit and mark
screw hole centers (Fig. 17). Punch or drill pilot holes in
the mounting surface for sheet metal screws.
Alternately, Tinnerman nuts can be used by making
clearance holes for the screws.
Mount Thermostat in unit.
Mount sensing bulb in unit using hangers (see Fig. 6).
BRANCH
SENSING
BULB
Fig. 17. Assembling thermostat, mounting bracket, and scale plate. (bracket from 316016B bag assembly shown.)
95-5559
MAIN
10 x 5/8-IN.
SHEET METAL SCREW (2)
MOUNTING BRACKET
2-3/4 (70)
Fig. 16. Mounting bracket in 316016 bag assembly.
Dimensions in inches (millimeters).
CAPILLARY
PROTECTED BARBS
THERMOSTAT
CONTROL SHAFT
6
5-5/16
(135)
5/8
(16)
2 (51)
C4649
MOUNT AS SHOWN OR TURN
90° TO ANY OF FOUR
POSITIONS AS REQUIRED.
SCALEPLATE
10-32 x 1/4-IN.
SCREW (2)
SETPOINT KNOB
C4651