Windsor High Efficiency Wood Stove
2" (51 mm)
Wall Line
8" (203 mm)
8"
(203 mm)
*16" (406 mm)
**18" (457 mm)
Figure 4
Floor Protector
Attach Handle Holder
ST1036
floor protection
Insert screw through handle holder and into lower left side
10/08
of stove (when facing the front). (Fig. )
Figure 5
Handle Holder
Handle
Mounting
Screw
6
2" (51 mm)
Chimney Connector
Floor
Protector
8"
(203 mm)
Door Side of
Appliance
ST1036
ST1038
Handle Holder
Stove Pipe
1. A clearance of 18" (457 mm) between the stovepipe
and combustible materials may be required. Check
with authorities having jurisdiction in your area.
2. All pipe sections must be connected with the male end
(crimped end) toward the stove.
3. Fasten the stove pipe to the flue collar by the use of
three (3) sheet metal screws. Do the same at each ad-
ditional joint to make the entire installation rigid.
4. Maintain the required diameter flue for the entire instal-
lation.
5. If you are connecting the stove to an old masonry flue,
be sure to have it inspected for cracks and general
condition.
6. It is recommended that no more than two (2) 90° bends
be used in the stove pipe installation. More than two
(2) 90° bends may decrease the amount of draw and
possibly cause smoke spillage.
7. A damper is not required in this installation. Remove
damper plate in the chimney or secure in the OPEN
position.
8. Single wall flue pipe assemblies must not exceed 10
feet (3 m) in horizontal run.
Chimney
CoNtACt yoUR LoCAL BUiLDiNG AUtHoRity foR
APPRoVED MEtHoDS of iNStALLAtioN.
1. This appliance requires a masonry or pre-manufac-
tured chimney listed to ULC S629 (Canada) and UL
103HT (US) sized correctly.
2. If a masonry chimney is used, it is advisable to have
your chimney inspected for cracks and check the gen-
eral condition before you install your unit. Relining may
be required to reduce the flue diameter to the appropri-
ate functional size.
3. To help ensure a good draft, the top of the chimney
should be at least 3 feet (914 mm) above the point
of penetration through the roof, and be at least 2 feet
(610 mm) higher than any point of the roof within 10
feet (3 m).
4. The chimney connector shall not pass through an attic,
roof space, closet, concealed space, floor, ceiling, wall
or any partition of combustible construction.
5. The minimum overall height of your chimney should be
15 feet (5 m) from the floor. (Fig. 6)
6. Do not use make shift compromises during installa-
tion.
Refer to chimney manufacturer's instructions.
30005128