7.2. Trouble Test.
Cover the Prism totally with a non-reflective material and confirm that the Detector indicates a Trouble
condition after approximately 10 seconds (the amber LED on the Detector will illuminate, and the Trouble
relay opening will indicate this). The Trouble condition will automatically reset after a period not greater
than 2 seconds when the obstruction is removed.

8. Connection and Configuration Settings.

8.1. Field Wiring.
The field-wiring interface is accessed through the back plate of the Detector Head (See Fig 4). The 2-pin
connector is the port for the Low Level Controller. The 8-pin connector is the interface to the field wiring
and is numbered left to right. Each unit is fitted with a 'flying' lead, with an 8-pin connector fitted (6 pins
used), for easy field wiring. See table below:
Pin Number
1
2
3
4
5
6
7
8
8.2. DIP Switch Settings.
Access to the configuration settings is through the back plate of the Detector Head (See Fig 4). Default
configuration settings are marked
50% Threshold
35% Threshold
25% Threshold
12% Threshold (Do Not Use – Future Requirement)
Latching Fire Relay
Auto Reset Fire Relay (5 seconds)
Fire Relay Enable On Compensation Limit
Fire Relay Disable On Compensation Limit
22318.10.03 15.09.05
Wire Color
n/a
BLUE
Fire relay common (COM) connection
YELLOW
Fire relay normally open (NO) connection
RED
Positive Supply (+10.2 to +30 Volts DC)
BLACK
Negative Supply (0V)
GREEN
Trouble relay normally closed (NC) connection
WHITE
Trouble relay common connection (COM) connection
n/a
.
Function
Signal Description
1
2
X
X
X
X
X
X
X
X
OFF
X
ON
X
X
OFF
X
ON
8
3
4
OFF
OFF
OFF
ON
ON
OFF
ON
ON
X
X
X
X
X
X
X
X

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for FFE Fireray 50RU

This manual is also suitable for:

Fireray 100ru

Table of Contents