11. Technical Data.
Operating Range Fireray 50RU
Operating Range Fireray 100RU
Lateral Coverage
Supply Voltage
Quiescent Current
Alarm/Trouble Current
Alarm Contacts
Trouble Contacts
Relay Contacts (all)
Alarm and Trouble Signal Delay
Power Down Reset Time
Operating Temperature
Moisture RH (max)
Fire Alarm Thresholds
Optical Wavelength
Head Maximum Size
Weight
12. Service / Application Notes.
Red LED indicates FIRE.
Continuous Amber LED indicates TROUBLE.
Flashing Amber LED once every 2 seconds indicates that the contamination/compensation function has reached its limit.
Alarm condition indicated by fire relay closing (relay contact is normally open).
Trouble condition indicated by Trouble relay opening (relay contact is normally closed).
Alarm may be latching or non-latching (default).
Periodic cleaning with a lint free soft cloth is required.
13. Parts List.
1 off: Detector Head Assembly with cable interface
1 off: Prism for the 50RU or 4 off: Prisms for the 100RU
1 off: Test Filter
14. Optional Extra Parts List.
Low Level Controller (Optional Extra Part Number 0400-01-XX, where XX is the latest version)
15. Technical Support.
Toll free hotline within USA 1-866-FIRERAY (347-3729)
E-mail:
sales@ffeuk.com
Website:
www.ffeuk.com
22318.10.03 15.09.05
15 to 160 Feet
160 to 330 Feet
30 Feet (either side of the beam)
10.2 to 30 Volts DC
Less than 4mA
Less than 20mA
Normally Open contacts rated 1 amps, 30 Volts DC, resistive
Normally Closed contacts rated 1 amps, 30 Volts DC, resistive
Maximum voltage 220 Volts DC, 30 watts, resistive
10 seconds
>5 seconds
32°F to 100°F
93% (non condensing)
2.50dB (25%), 3.74dB (35%), 6.02dB (50%)
880nm
Width 5.1 inches, Height 8.25 inches, Depth 4.7 inches
24 ounces
11