Technical Bulletin
FEATURES
Microprocessor controlled
50RU Range 15 – 160 Feet
100RU Range 160 – 330
Feet
Unique simple alignment
12VDC or 24VDC operating
voltage
Selectable Alarm thresholds
Low current consumption
Automatic reset
Automatic contamination
compensation
Low Level Controller
Interface option

Advertisement

Table of Contents
loading

Summary of Contents for FFE Fireray 50RU

  • Page 1 FIRERAY 50/100RU Technical Bulletin FEATURES • Microprocessor controlled • 50RU Range 15 – 160 Feet • 100RU Range 160 – 330 Feet • Unique simple alignment • 12VDC or 24VDC operating voltage • Selectable Alarm thresholds • Low current consumption •...
  • Page 2: System Description

    1. System Description. Fireray 50/100RU Detector comprises a Transmitter and Receiver contained within one enclosure. The Detector installs to the building fabric between 1 and 2 feet from the ceiling. The Transmitter emits an invisible infrared light beam that is reflected via a prism mounted directly opposite and with a clear line of sight.
  • Page 3: Detector Positioning

    3. Detector Positioning. An infrared signal is projected out of the transmitter optics (see Fig 3) to the reflector placed at the opposite end of the detection zone. The signal is reflected back to the receiver where it is analysed for fire and Trouble.
  • Page 4: Installation

    Due to the principle of the detector i.e. reflective, the prism must NOT be mounted on glass or a polished reflective surface. Mount the Prism on a solid structure between 15 to 160 feet (Fireray 50RU), and 160 to 330 feet (Fireray 100RU) directly opposite the Detector.
  • Page 5 5. Prism Targeting Mode. Apply power to the Detector. There is a 5 seconds pre-charge delay after power is applied to allow the internal circuits to stabilise correctly. After this period the RED indicator will flash once to indicate that the model is a 50RU or will flash twice to indicate a 100RU.
  • Page 6 • FLASHING AMBER The Detector is receiving a weak signal and is attempting to increase the infrared power output. • The Detector has optimised the infrared power and receiver gain for the current orientation of the Detector and Prism. This does not mean that the Detector to Prism alignment is at its optimum, i.e.
  • Page 7 6.3. Alignment Process Flow Diagram. Select alignment mode AMBER LED will illuminate for 5 seconds Constant AMBER Return To Prism Wait until both LED’s stop Targeting Mode flashing (up to 30 seconds) Slowly adjust a thumbwheel in one direction and observe the LEDs Amber Stop turning the...
  • Page 8: System Testing

    6.4. Exiting Alignment Mode. Do not remove the detector from the wall during this action. Using the mode switch (See fig. 4) select Run Mode (Switch will be in the down position). On exiting alignment mode the Detector will perform an internal calibration check, this can take up to 60 seconds.
  • Page 9: Connection And Configuration Settings

    7.2. Trouble Test. Cover the Prism totally with a non-reflective material and confirm that the Detector indicates a Trouble condition after approximately 10 seconds (the amber LED on the Detector will illuminate, and the Trouble relay opening will indicate this). The Trouble condition will automatically reset after a period not greater than 2 seconds when the obstruction is removed.
  • Page 10: Zone Wiring

    9. Typical single zone wiring diagram. ZONE WIRING 10.2 to 30 Volts DC (RED) FIRERAY 0V (BLACK) Alarm Resistor Fire Relay NO (YELLOW) COM (BLUE) Trouble Relay COM (WHITE) End of Line Component NC (GREEN) This diagram is an example for a single Fireray being the only device on a zone. The correct operation for Fire and Trouble should always be checked connected to a typical panel.
  • Page 11 10. Detector Interface Assembly Configuration Settings (not to scale). 1 2 3 4 DIP SWITCH SETTINGS 2-pin port for optional Low Fig. 4. Level Controller 22318.10.03 15.09.05...
  • Page 12 11. Technical Data. • Operating Range Fireray 50RU 15 to 160 Feet • Operating Range Fireray 100RU 160 to 330 Feet • Lateral Coverage 30 Feet (either side of the beam) • Supply Voltage 10.2 to 30 Volts DC •...