10.3.2.10 IPM module protection(ODU P6)

IPM module protection
Check whether the voltage range 
of P-N on IPM module is normal? 
DC277-356V for 18-27KBtu/h; 
DC277-410V for 36-42KBtu/h
Yes
Check whether the connecting 
line between main board and 
the IPM module is connected 
tightly
Yes
Check whether the connecting 
line of the compressor is 
connected correctly or tightly
Yes
Replace the IPM module, 
check whether the system can 
work normally?
No
Check if the outdoor fan 
runs properly or the outdoor 
unit ventilation is good.
No
Replace the main board; check 
whether the system can work 
normally?
No
Replace the compressor, check 
Yes
whether the system can work 
normally?
 
No
Connect it tightly, 
No
check ok or not?
No
Connect it well, check 
No
ok or not?
No
Check whether the resistance of 
the  fan  motor  is  normal.  If  not, 
replace  the  fan  motor. 
For  other 
efer  to  the  solution  of 
Yes
models,  r
fan  speed  has  been  out  of 
control  malfunction  .  F i n d   o u t 
the cause and have it solved.
Yes
Yes
Check whether the input 
power supply is correct? 
208-230V, 1N, 60Hz
Yes
Check whether the 
power supply line is 
connected correctly and 
tightly
Yes
Check whether the lines 
in E-part box are 
connected tightly
Yes
Check whether the bridge rectifiers are 
normal? Use the multimeter to measure 
the resistance between each two 
terminals, check whether there is the 
condition that value of resistance is 0
Yes
Check  whether  the  connecting  line  of 
every  reactor  is  normal?  If  the  line  is 
broken, the resistance of the two ports is 
∞(models  except  for  M4OA-36HFN1-
Q,M4OD-28HFN1-Q, 
Q);Check  whether  the  PFC  module 
broken  (for  M4OA-36HFN1-Q,M4OD-
28HFN1-Q, 
M5OC-36HFN1-Q,M50D-
42HFN1-Q)
Trouble is solved
Regulate it to correct, then 
No
check whether the system 
can work normally?
No
Connect it correctly 
No
and tightly, check ok 
or not?
No
Connect it tightly, 
No
check ok or not?
No
No
Yes
Replace the bridge rectifiers
M5OC-36HFN1-
No
Replace the connecting line or 
reactor or replace the PFC 
module(for M4OC-36HRFN1-
M,M50D-42HFN1-Q)