Model
Maximum system voltage (DC)
Rated input voltage (DC)
Range of operating DC voltage (DC)
Maximum array short circuit current (DC)
Maximum operating current (DC)
Nominal output voltage (AC)
Operating voltage range (AC)
Nominal output frequency (AC)
Operating frequency range (AC)
Maximum continuous output current (AC)
Maximum continuous output power (AC)
Rated output power
Peak conversion efficiency (%)
Power factor
Total harmonic distortion [ THD ] (%)
Operating temperature
Dimension
Weight
Enclosure type
Solar power conditioner system
Switching system
Insulator system
Electric system
Grid-connected protection
Ground fault protection
* Bracket included
29
Specification
380 V
240 V
110 V to 350 V
10 A
22.5 A (7.5A for a DC input × 3)
240 V
211 V to 264 V
60 Hz
59.3 Hz to 60.5 Hz
15 A
3500 W
3000 W
92 %
More than 0.95 (more than rated output power 1/8)
Less than 5%
-4°F_to_104°F_(-20˚C to +40˚C)
Solar Power
Conditioner
32°F_to_104°F_(0˚C to +40˚C)
Solar Power
Conditioner
Display
Width-x-Height-x-Depth_(23.62x17.72x7.56_inches)_(600×450×192_mm)
Solar Power
Conditioner
Width-x-Height-x-Depth_(5.39x4.61x0.79_inches)_(137×117×20_mm)
Solar Power
Conditioner
Display
Approx._62_pounds_(Approx. 28 kg*)
Solar Power
Conditioner
0.5_pounds_(Approx. 0.2 kg)
Solar Power
Conditioner
Display
3 R
Main Circuit System
Voltage stiff current control system
PWM (pulse width modulation) system
Built-in high frequency insulating transformer system
1-phase 2-wire system(connected to 1-phase 3-wire system)
Protection
AC Over Voltage / Under Voltage, AC Over Frequency / Under Frequency detection
anti-islanding component (IEEE929)
DC detector / interrupter
JH-3500U