Rectifying faults
Error EA
EA
and
flashing.
During operation: flame not detected
Check
1.
Is a burner flame visible?
2.
Is the gas cock turned on?
3.
Is there air in the supply pipe?
4.
Natural gas models:
does the building have a supply pressure
regulator?
LPG models:
is the flow rate of the gas supply to the
appliance correct?
5.
Is the earth connection correct?
6.
Is the condensation trap blocked?
28
Supplied By www.heating spares.co Tel. 0161 620 6677
Action
↓5.
yes:
↓2.
no:
↓3.
yes:
B Open the gas cock.
no:
B Press
, restart the appliance.
EA? ↓3.
B Vent supply pipe.
yes:
B Press
, restart the appliance.
EA? ↓4.
↓4.
no:
B Check that it is fitted correctly and functioning prop-
yes:
erly and correct if necessary.
B Check supply pressure, inform gas company if outside
correct range.
B Is correct code plug fitted?
B Press
, restart the appliance.
EA? ↓5.
↓5.
no:
↓5.
yes:
B Is there enough gas in the supply cylinder?
no:
B Is there air in the supply pipe?
B Is the solenoid valve in the "meter cabinet" opening?
B Is the supply pressure OK? (if the supply pressure is
too high, check the pressure regulator in the "meter
cabinet" and on the LPG supply cylinder)
B Press
, restart the appliance.
EA? ↓5.
↓6.
yes:
B Correct the electrical connection.
no:
B Press
, restart the appliance.
EA? ↓6.
B Clean out condensation trap discharge pipe.
yes:
B Press
, restart the appliance.
EA? ↓11.
↓7.
no:
7 181 465 347 (05.01)