Technical Data - Bosch Fireray 50 Product Information

Linear smoke detector
Hide thumbs Also See for Fireray 50:
Table of Contents

Advertisement

Product Information Linear Smoke Detector Fireray 50/100RV

10. Technical Data

Operating voltage
Current consumption:
- in standby mode
in standby mode
- in alarm/malfunction
Reset control by power disruption
Alarm relay
Fault relay
Permissible distance between the detector and the
prism reflector:
- Fireray 50R
- Fireray 100R
Optical wavelength
Adjustable alarm threshold values
Axial deviation tolerance
(at 35% sensitivity)
Operating temperature
Protection type
Dimensions (W x H x D)
Weight
Housing:
- Color
- Material
VdS ID number
Seite 19 von 22
PI - 34.85
10 V DC . . . 30 V DC
< 4 mA @ 24 V
< 4 mA @ 24 V
< 15 mA
> 5 s
Open contact, potential-
free
(2 A @ 30 V DC)
Break contact element,
potential - free
(2 A @ 30 V DC)
5 m to 50 m
50 m to 100m
880nm
2.50 dB (25%)
3.74 dB (35%)
6.02 dB (55%)
Detector $0.8_
Prism reflector $5.0_
- 30_C . . . +55_C
IP 50
126 x 210 x 120 mm
670 g
light gray/black
ABS, non- flammable
G 203 070
601-F.01U.002.705
A1.en / 29.12.2004
ST-FIR/ PRM1/ zab

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fireray 100 rv

Table of Contents