Venting; Venting Lengths And Components - Napoleon BGD42CFN Installation And Operating Instructions Manual

Table of Contents

Advertisement

8

3.0 VENTING

RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET
FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 5" EXHAUST / 8" AIR INTAKE VENT PIPE SYSTEM.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Vent lengths that pass
through unheated spaces (attics, garages, crawl spaces) should be insulated with the insulation wrapped in
a protective sleeve to minimize condensation. Provide a means for visually checking the vent connection to
the appliance after the appliance is installed. Use a fi restop, vent pipe shield or attic insulation shield when
penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
REQUIRED RISE ON HORIZONTAL VENTING
RIGID VENTING
FLEXIBLE VENTING
For optimum performance, it is recommended that all horizontal runs have a 1" rise per foot.
3.1

VENTING LENGTHS AND COMPONENTS

Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab
venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and
air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-
Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided
with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the
corresponding supplier:
PART
Duravent
Amerivent
Direct Temp
SuperSeal
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
procedure found on the website for your venting supplier.
W415-0779 / A / 04.27.10
Refer to the section applicable to your installation.
5"/8"
SUPPLIER
W175-0170
Wolf Steel
5DSC-N2
American Metal
5DT-AA
Selkirk
5DDA
Metal-Fab
WARNING
!
BGD42CF
0"
0"
WEBSITE
www.duravent.com
www.americanmetalproducts.com
www.selkirkcorp.com
www.mtlfab.com
7.2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bgd42cfp

Table of Contents