Checking The Gas Flow Rate; Check Gas Setting - Vaillant atmoSTOR VGH classic 130/6 Z Instructions For Use And Installation

Gas-fired hot water cylinders
Table of Contents

Advertisement

Available languages

Available languages

5.4 Checking the gas flow rate (volumetric method)
• Take all other gas appliances which are connected by
the same gas meter out of operation
• Start the cylinder as shown and set the temperature
selector to „7" (when the appliance has been heated
up, tap hot water in order to reduce the storage water
temperature and to take the burner into operation)
• Read off flow in l/min at the gas meter for one minute
(measure time with timer of possible
• Compare the measured gas flow value with the requi-
red values in the tables
In the case of deviations of less than
± 7.5%, it is not necessary to take any measures.
• If the measured value exceeds the value by ± 7.5%,
check the throttle and the injector according to the
tables
If no irregularities are determined during this
check and if there is no fault in the gas supply
after consulting the competent gas supply com-
pany, the after-sales service is to be contact.
1. Gas family: nat. gas, group (GZ50); factory-set for W s (W o ) = 15,0 kWh/m
atmoSTOR
Rated
input
[kW]
VGH classic 130
8,4
VGH classic 160
9,2
VGH classic 190
10,0
2. Gas family: nat. gas, group L (GZ41), (GZ35 lower input); factory-set for W s (W o ) = 12,4 kWh/m
atmoSTOR
Rated
input
[kW]
VGH classic 130
8,4
VGH classic 160
9,2
VGH classic 190
10,0
3. Gas family: LPG, B/P; G 30/31 – 30/37 mbar
atmoSTOR
Rated
input
[kW]
VGH classic 130
8,4
VGH classic 160
9,2
VGH classic 190
10,0
4. Gas family: LPG, B/P; G 30/31 – 50 mbar
atmoSTOR
Rated
input
[kW]
VGH classic 130
8,4
VGH classic 160
9,2
VGH classic 190
10,0
Gas-fired hot water cylinders atmoSTOR VGH classic
5.5 Check gas setting (burner pressure test method)
• Close the gas shut-off valve
• Unscrew the sealing screw at the burner pressure test
point (1)
• Connect the pressure gauge to the burner pressure
test point (1)
• Open the gas shut-off valve
• Measure the burner pressure
• Take the appliance into operation
In case of deviations of ± 15% of the values given in the
following table, there is no need for action. In case of
deviations exceeding ± 15%, check the throttle jet and
the burner nozzle based upon the following tables. In
case everything is o.k., and your gas supplier informs you
that there is not any trouble in the gas supply, contact
your after-sales service.
• Turn the control knob to the „off position" (•)
• Close gas shut-off valve
• Take off pressure gauge
• Seal burner bressure test point (1) with sealing screw
Check the gas tightness
Throttle gas
Pilot burner
section
nozzle
marking
marking
280
32
222
32
222
32
Throttle gas
Pilot burner
section
nozzle
marking
marking
222
32
224
32
226
32
Throttle gas
Pilot burner
section
nozzle
marking
marking
230
23
220
23
220
23
Throttle gas
Pilot burner
section
nozzle
marking
marking
170
23
190
23
190
23
Commissioning 5
, n.c.v. = 9,5 kWh/m
3
Burner
Gas flow
nozzle
marking
[l/min]
280
14,7
280
16,1
305
17,5
, n.c.v.= 8,5 kWh/m
3
Burner
Gas flow
nozzle
marking
[l/min]
280
16,5
280
18,0
305
19,6
Burner
Gas flow
nozzle
marking
[l/min]
155
4,4/5,8
155
4,8/6,3
170
5,2/6,8
Burner
Gas flow
nozzle
marking
[l/min]
155
4,4
155
4,8
170
5,2
GB
3
Burner
pressure
[mbar]
7,4
9,3
8,4
3
Burner
pressure
[mbar]
10,7
11,5
11,4
Burner
pressure
[mbar]
21,0/26,9
24,7/31,4
23,7/30,4
Burner
pressure
[mbar]
20,0
26,8
23,0
11