Checking The Gas Flow Pressure - Vaillant atmoMAG MAG mini 114/1 I Installation And Maintenance Instructions Manual

Table of Contents

Advertisement

6 Start-up
2
Start up the product with the product casing attached.
Turn the temperature selector (1) clockwise as far as it
goes and turn the rotary power switch (2) anti-clockwise
as far as it goes in order to set the lowest water volume
and the maximum gas volume.
Open a hot water tap.
Ensure that the water pressure is at least 0.13 MPa
(1.3 bar) during the test.
Operate the product until a steady state is reached (ap-
prox. 10 minutes).
Block off the flue gas route with a Vaillant flue gas re-
strictor, for example. Also observe the documentation
enclosed with the flue gas restrictors.
The flue gas sensor must automatically interrupt the
gas supply within two minutes.
Close the hot water tap.
Allow the flue gas sensor to cool for at least 10 minutes.
Start up the product again.
1
Clear any faults from the product by opening the hot wa-
ter tap again and switch the product on and off again by
pressing the main switch (1) a second time.
If the fault clearance does not work or the product is re-
peatedly blocked by a safety device, check the product or
contact Vaillant Customer Service.
In this case, shut down the product.
12
1
6.6

Checking the gas flow pressure

1
Close the gas stopcock.
Unscrew the sealing screw (1) from the test nipple on the
gas valve assembly.
Remove the seal.
Connect a manometer to the test nipple on the gas valve
assembly.
Open the gas stopcock.
Start up the product in accordance with the operating
instructions and draw off domestic hot water.
Measure the gas flow pressure.
Applicability: Germany
OR Austria
Gas family
Liquid gas
G31
Conditions: Gas connection pressure not in the permissible range
Danger!
Risk of material damage and operating
faults caused by incorrect gas flow pres-
sure.
If the gas flow pressure lies outside the per-
missible range, this can cause operating
faults in and damage to the product.
Do not make any adjustments to the
product.
Check the gas installation.
Do not start up the product.
If you are unable to eliminate the fault, contact the gas
supply company.
Close the gas stopcock.
Remove the manometer.
Installation and maintenance instructions atmoMAG 0020273765_00
Permissible gas flow pres-
sure
4.25–5.75 kPa
(42.5–57.5 mbar)