Mitsubishi Electric PUMY-P112VKM1 Service Manual page 52

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM1:
Table of Contents

Advertisement

Check code
Low pressure trouble
1300
Chart 3 of 3
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Continued from the previous page
Check the resistance of SV1.
Replace the SV1.
Is there a resistance detected?
No
Yes
<63L equipped model>
Is the connector for outdoor multi
controller circuit board 63L
Reconnect the connector or connect it tightly.
Yes
disconnected or loose?
No
Replace the outdoor multi controller circuit
board.
52
OCH576

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents