8-1-3. Countermeasures for Error During Test Run

• If a problem occurs during test run, a code number will appear on the remote controller (or LED on the outdoor unit), and the
air conditioning system will automatically cease operating.
Determine the nature of the abnormality and apply corrective measures.
Check
code
0403
Serial communication error
1102
Compressor temperature
1300
Low pressure
1302
High pressure
1500
Superheat due to low discharge temperature
Refrigerant shortage
1501
Blocked valve in cooling mode
1508
4-way valve trouble in heating mode
2500
Water leakage
Drain over flow protection
2502
2503
Drain sensor abnormality
4100
Compressor current interruption (locked compressor)
4210
Compressor overcurrent interruption
Undervoltage/overvoltage/PAM error/L1open phase/power
4220
synchronization signal error
4230
Heat sink temperature
4250
Power module
4400
Rotational frequency of outdoor fan motor
Air inlet thermistor trouble (TH21) or
5101
Compressor temperature thermistor (TH4) open/short
Liquid pipe temperature thermistor trouble (TH22)
5102
Suction pipe temperature thermistor (TH6) open/short
5103
Gas pipe temperature thermistor trouble (TH23)
5105
Outdoor liquid pipe temperature thermistor (TH3) open/short
5106
Ambient thermistor (TH7) open/short
5109
HIC pipe temperature thermistor (TH2) open/short
5110
Heat sink temperature thermistor (TH8) open/short
5201
High pressure sensor (63HS)
5202
Low pressure sensor (63LS)
5300
Primary current
Contact failure of drain float switch
5701
6600
Duplex address error
6602
Transmission processor hardware error
6603
Transmission bus BUSY error
6606
Signal communication error with transmission processor
6607
No ACK error
6608
No response frame error
6831
MA communication receive error (no receive signal)
6832
MA communication send error
6833
MA communication send error
6834
MA communication receive error
7100
Total capacity error
7101
Capacity code error
7102
Connecting excessive number of units
Address setting error
7105
Note:
When the outdoor unit detects No ACK error/No response error, an object indoor unit is treated as a stop, and not assumed to be abnormal.
*Abnormality for PWFY series
Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
Bit
1
2
Compressor
Indication
52C
operated
OCH576
Trouble
3
4
5
21S4
SV1
(SV2)
Detected Unit
Remote
Indoor
Outdoor
Controller
Outdoor unit outdoor multi controller circuit board –
Power circuit board communication trouble
Check delay code 1202
Check delay code 1402
Check delay code 1600
Check delay code 1601
Check delay code 1501
Check delay code 1608
Check delay code 4350
Check delay code 4320
Check delay code 4330
Check delay code 4350
Check delay code 4500
Check delay code 1202
Check delay code 1211
Check delay code 1205
Check delay code 1221
Check delay code 1222
Check delay code 1214
Check delay code 1402
Check delay code 1400
Check delay code 4310
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected. *
Only M-NET Remote controller is detected. *
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
6
7
8
Always lit
46
Remarks
[Example]
When the compressor and
SV1 are turned during cooling
operation.
1 2 3 4 5 6 7 8