Mitsubishi Electric PUMY-P112VKM1 Service Manual page 33

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM1:
Table of Contents

Advertisement

• Name, Symbol, and the Maximum Units for Connection
• Longest length via outdoor units : L
• Longest transmission cable length : L
• M-NET Remote controller cable length : R
M1 M2 S
M1 M2 S
Power Supply
A : Group
B : Group
C : Group
D : Shielded Wire
E : Sub M-NET Remote Controller
( ): Address example
• Never connect together the terminal blocks (TB5) for transmission wires for M-NET control indoor units (M-IC) that have
been connected to different outdoor units (OC).
• Set all addresses to ensure that they are not overlapped.
• M-NET remote controller and MA remote controller cannot be connected with the M-NET control indoor unit of the same
group wiring together.
OCH576
+L
+L
+L
L
1
2
3
4,
L
+L
, L
1,
3
4
3+
, R
,R
1
2
If the length exceeds 10 meters, use a 1.25 mm² shielded wire. The length of this sec-
tion (L
) should be included in the calculation of the maximum length and overall length.
8
OC
(51)
TB3
TB7
M1 M2 S
D
OC
(53)
NO
TB3
TB7
M1 M2 S
Unit
M1 M2 S
System
controller
M1 M2 S
[ 500 meters (1.25 mm²)
+L
+L
L
L
+L
+L
+L
1
2
3+
5,
1
2
6
7
[ 200 meters (1.25 mm²)
L
, L
L
+L
, L
5
6,
2
6
7
[ 10 meters (0.5 to 1.25 mm²)
, R
+R
2
3
4
A
M-IC
M-IC
(01)
(02)
TB5
TB5
M1 M2 S
M1 M2 S
A B
(101)
M-NET RC
M-IC
M-IC
(04)
(03)
TB5
TB5
M1 M2 S
M1 M2 S
A B
(104)
M-NET RC
B
33
C
M-IC
M-IC
(05)
(06)
TB5
TB5
M1 M2 S
M1 M2 S
A B
A B
(105)
(155)
M-NET RC M-NET RC
NO
E
M-IC
(07)
TB5
M1 M2 S