ELECTRICAL WIRING

This chapter provides an introduction to electrical wiring for the CITY MULTI-S series, together with notes concerning power
wiring, wiring for control (transmission wires and remote controller wires), and the frequency converter.

9-1. OVERVIEW OF POWER WIRING

Use a separate power supply for the outdoor unit and indoor unit.
(1)
Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
(2)
The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
(3)
Make sure the power-supply voltage does not drop more than 10 %.
Specific wiring requirements should adhere to the wiring regulations of the region.
(4)
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57).
(5)
For example, use wiring such as YZW.
Install an earth longer than other cables.
(6)
Warning:
Be sure to use specified wires to connect so that no external force is imparted to terminal connections. If connections are not fixed firmly,
·
it may cause heating or fire.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct
·
current.
Caution:
Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric
·
shock.
Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a
·
malfunction of unit or fire.
Be sure to install N-Line. Without N-Line, it could cause damage to the unit.
·
9-2. WIRING OF MAIN POWER SUPPLY AND EQUIPMENT CAPACITY

9-2-1. Wiring diagram for main power supply

■ Schematic Drawing of Wiring : When NOT using a Branch Box (example)
PUMY-P•VKM1 series
~/N 220/230/240 V, 50 Hz
~/N 220 V, 60 Hz
PUMY-P•YKM1 series
3N~380/400/415 V, 50Hz
Grounded
Schematic Drawing of Wiring : When using a Branch Box (example)
<When power is supplied from the outdoor unit>
PUMY-P•VKM1 series
A
/N 220/230/240 V
PUMY-P•YKM1 series
A
3N~380/400/415 V, 50Hz
Grounded
OCH576
B
~/N 220/230/240 V, 50 Hz
A
~/N 220 V, 60 Hz
L/N
;
B
A
Note: The M-NET control indoor unit cannot receive power
L1/L2/L3/N
supplied from an outdoor unit, so provide it with power
separately.
;
B
;
L/N
B1/B2
;
B
;
L1/L2/L3/N
B1/B2
;
A
L/N
E
;
C
S1/S2/S3
;
D
;
L/N
S 1/S2/S3
D
;
S1/S2/S3
D
;
;
C
;
S1/S2/S3
D
;
L/N
S1/S2/S3
D
;
S1/S2/S3
;
131
F
L/N
L/N
E
E
;
;
A Switch (Breakers for Wiring and Current Leakage)
B Outdoor Unit
C Branch Box
D A-Control Indoor Unit
E M-NET Control Indoor unit
F Pull Box
L/N
E
;