Basic function parameter list

6.

FUNCTION LIST

6.1 Basic function parameter list
Param
Name
eter
0
Torque boost
Maximum
1
frequency
Minimum
2
frequency
3
Base frequency
Multi-speed set-
4
ting (high speed)
Multi-speed set-
5
ting (middle speed)
Multi-speed set-
6
ting (low speed)
7
Acceleration time
8
Deceleration time
Electronic
9
thermal O/L relay
Extended function
30
display selection
Operation mode
79
selection
Remarks
•Setting "1" in Pr. 30 "extended function display selection" makes the extended function
parameters valid. (Refer to page 18.)
•The decimal places of a value of 100 or more (3 digits or more) cannot be set to be displayed.
Setting
Indication
Range
0 to 15%
0 to 120Hz
0 to 120Hz
0 to 120Hz
0 to 120Hz
0 to 120Hz
0 to 120Hz
0 to 999s
0 to 999s
0 to 50A
0, 1
0 to 4, 7, 8
28
Minimum
Factory
Setting
Setting
Increments
0.1%
6%
0.1Hz
60Hz
0.1Hz
0Hz
0.1Hz
60Hz
0.1Hz
60Hz
0.1Hz
30Hz
0.1Hz
10Hz
0.1s
5s
0.1s
5s
Rated output
0.1A
current
1
1
Customer
Setting
0
0

Advertisement