Installation Method; Installation Of The Inverter - Mitsubishi Electric FR-S500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-S500:
Table of Contents

Advertisement

Installation of the inverter

2.

INSTALLATION METHOD

2.1 Installation of the inverter
Enclosure surface mounting
Leave enough clearances
and provide cooling measures.
Install the inverter under the following conditions.
Vertical mounting
Vertical
Inverter consists of precision mechanical and electronic parts. Never install or han-
dle it in any of the following conditions as doing so could cause an operation fault or
failure.
Direct sunlight
Vertical mounting
(when mounted
inside enclosure)
Fix the front
cover and wiring
cover after
removing them.
Ambient temperature
and humidity
Temperature: -10°C to 50°C
Humidity: 90%RH maximum
Measurement
position
Inverter
5cm
Measurement position
5cm
Vibration
High temperature,
2
(5.9m/s
or more)
high humidity
Transportation
Oil mist, flammable
by holding front
gas, corrosive gas,
cover or dial
fluff, dust, etc.
4
Mounting inside enclosure
When containing two or more
inverters, install them in parallel
and provide cooling measures.
1cm
or more
10cm
or more
These clearances are also
necessary for changing the
cooling fan. (
5cm
more is provided with a
cooling fan.
Horizontal placement
Mounting to
combustible material
Clearances
10cm
or more
1cm
or more
The 1.5K or
)

Advertisement

Table of Contents
loading

Table of Contents