Precautions for maintenance and inspection
Inspection
Inspection Item
Item
(1) Check
Operation
check
(2) Perform
(1) Check for
Cooling
fan
(2) Check for loose
(1) Check for LED
(2) Cleaning
Indication
Check that reading
is normal.
Meter
(1) Check for
General
(2) Check for
(1) Check with
Insulation
resistance
*Consult us for periodic inspection.
Interval
Periodic*
balance of
output
voltages
across
phases with
the inverter
operated
alone.
sequence
protective
operation test
to ensure no
fault in
protective
and display
circuits.
unusual
vibration and
noise.
screws and
bolts
lamp blown.
unusual
vibration and
noise.
unusual odor.
megger
(across
terminals and
earth (ground)
terminal).
Method
Criterion
(1) Measure
(1) Phase-to-
voltages
phase
across the
voltage
inverter
balance
output
within 4V for
terminals
200V
U-V-W.
(2) Fault must
(2) Simulatively
occur
short or
because of
open the
sequence.
protective
circuit
output
terminals of
the inverter.
(1) Turn by hand
No unusual
with power
vibration and
off.
noise.
(2) Visual check
(1) Lamps
(1) Check that the
indicate
lamps are lit.
indicator
lamps on
panel.
(2) Clean with
rag.
Check the
Must satisfy
readings of the
specified and
meters on the
management
panel.
values.
(1) Auditory,
(1), (2) No fault
sensory,
visual
checks.
(2) Check for
unusual odor
due to
overheat,
damage, etc.
(1) Disconnect
(1) 5MΩ or more 500V megger
cables from
U, V, W
(including
motor
cables)
54
Instrument
Digital
multimeter,
rectifier type
voltmeter
Voltmeter,
ammeter,etc.