Checking Outputs (Relay Test) - Viessmann Vitotronic 200 Operating Instructions Manual

Vitodens 200-w, b2ha models 45 to 150 wall-mounted, gas-fired condensing boiler in conjunction with the vitotronic 300-k mw2c cascade control for operation with natural gas and liquid propane gas heating input 55 to 530 mbh 16 to 150 kw read and s
Table of Contents

Advertisement

Scanning Options

Checking Outputs (Relay Test)

1. Press OK and
simultaneously for approximately
4 seconds.
2. "Actuator test"
The following relay outputs can be controlled subject to system design:
Display
All actuators
Base load
Full load
Output, internal
Output 21/28
Outp. int. exten. H1
EA1 output 1
14
Explanation
Off
All actuators are off.
On
Burner operated at minimum output; circulation pump sÖ is started.
On
Burner operated at maximum output; circulation pump sÖ is started.
On
Output sÖ active.
On
Output sA active.
On
Output 28/20 active.
On
Contact P - S at plug aBJ of extension EA1 closed.
Vitotronic 200 Operating