Download Print this page

Weil-McLain 380 User Manual page 18

Water & steam boilers for gas, light oil, & gas/light oil-fired burners
Hide thumbs Also See for 380:

Advertisement

Weil-McLain 80 Boiler For Gas, Light Oil, Gas/Light Oil Fired Burners
8
Model 1080 through 1280 steam boiler piping — NOTE minimum 24 inches between boiler water line and
bottom of header.
Condensate piping to boiler
18
Condensate receiver capacity
Boiler
AHRI
Gallons
model
gross
condensate
number
output
per hour
15-minute
(lbs steam
per hour)
operation
380
278
33
480
396
48
580
515
62
680
634
76
780
753
90
880
872
105
980
991
119
1110
133
1229
148
1348
162
Note 1 — Maximum time to when condensate returns to boiler.
(continued)
Minimum condensate receiver
capacity (gallons) (Note 1)
30-minute
45-minute
60-minute
boiler
boiler
boiler
boiler
operation
operation
operation
11
21
31
41
15
29
43
58
19
38
56
75
23
46
69
92
28
55
82
109
32
63
95
126
36
72
108
143
40
80
120
160
45
89
133
178
49
98
146
195
Part No. 550-141-935/0215
Recommended
condensate
feed pump
capacity
GPM at 15 PSI
1.2
1.6
2.1
2.6
3.1
3.5
4.0
4.5
5.0
5.4

Advertisement

loading

This manual is also suitable for:

480680780880580980 ... Show all