Before Installing Boiler Installation must comply with: Before selecting boiler location: Provide combustion and ventilation air openings: Grating – Min. 12" above avg. snowline Note: GRADE Size of areaway and grating to be equal to or greater than total louver area. Areaway Louver Figure 1 Combustion and Ventilation Air...
Page 4
Before Installing Boiler Provide clearances for servicing around boiler: Boiler Model 2" Min. Lay a foundation, if needed: Boiler Foundation Length Table “L” Boiler Inches Model 1078 1178 1278 “L” 30" Figure 3 Boiler Foundation “L” Inches...
Assemble Block Install back refractory blanket: Prepare back section: Sealing rope Cut off rope even with edge Cut off rope even with edge 3 1/2” Sealing ring Cut off rope even with edges Figure 4 7 1/2" Sealing ring Sealing rope Cut out observation...
Page 8
Assemble Block Prepare remaining sections: Section Arrangement Table Maximum Section Arrangement Boiler No. of (all heaters must be Model Heaters on left side of boiler) 378 W&S F-TI-B 478 W&S F-TI-I-B 578 W&S F-TI-I-TI-B 678 W&S F-TI-I-TI-I-B 778 W&S F-TI-I-TI-I-I-B 878 W&S F-TI-I-TI-I-I-TI-B 978 W&S...
Page 10
Assemble Block Prepare flue collector hood assembly: Flat-stitched sealing rope Bend rope do not cut or stretch Flue collector hood end cap Figure 9 Sealing Rope Application on Collector Hood Assembly Double-faced tape applied to flange Extend rope 1/4" past open ends Flue collector hood modules...
Recommended Minimum Pipe Sizes for Known Flow Rates Water System Flow Rate supply (front only) Up to 35 36 to 50 51 to 77 78 to 142 Water meter valve ASME Drain Valve Size Boiler Model 378-478 578-1178 1278 Supply...
Connect Steam Boiler Piping General steam piping information: • Cold Check water fill Water meter valve Manual isolation valve Pressure reducing valve (when used) Manual isolation valve Figure 14 Cold Water Fill Piping Fig. Boiler Model 1078-1278 Install piping: To condensate return piping or condensate receiver...
Make Final Adjustments To fill water boilers: To fill steam boilers: Breeching damper Adjust burner and breeching damper: Test Plug Figure 29 Breeching Damper Adjustment Lock (Slide down to open damper)
Page 26
Make Final Adjustments Skim steam boilers: Determine if water treatment is needed (water boilers only): Check boiler for gas-tight seal:...
Data and Dimensions Supply Tappings Quantity And Size* Boiler Model Water Steam 2 - 4" 2 - 4" 2 - 4" 2 - 4" 2 - 4" 2 - 4" 2 - 4" 2 - 4" 2 - 4" 2 - 4" 2 - 4"...
Page 28
Data and Dimensions Minimum for heater removal 3" NPT 3" NPT return return Front Back Water line 4" NPT supply outlets W=Boiler section length Side Intermediate...