Battery Installation And Replacement; Mounting The Alarm; Sliding The Alarm On The Mounting Plate; Vertical Mounting - Interlogix 600-6520-95 Manual

Carbon monoxide alarm
Table of Contents

Advertisement

Do not install in kitchens, garages, or furnace rooms that
may expose the sensor to substances that could damage
or contaminate it.
Do not install in areas where the temperature is colder
than 40°F (4.4°C) or hotter than 100°F (37.8°C) such as
crawl spaces, attics, porches, and garages.
Do not install within 5 ft. of heating or cooking appliances.
(We recommend 15 ft. to prevent nuisance alarms.)
Do not install near vents, flues, chimneys, or any
forced/unforced air ventilation openings.
Do not install on metal surfaces.
Avoid mounting in areas with a large quantity of metal or
electrical wires.
Do not install near ceiling fans, doors, windows, or areas
directly exposed to the weather.
Do not install in dead air spaces, such as peaks of vaulted
ceilings or gabled roofs, where CO may not reach the
sensor in time to provide early warning.
Do not install near deep-cell large batteries. Large
batteries have emissions that can cause the alarm to
perform at less than optimum performance.
Do not obstruct the vents located on the alarm. Do not
place the alarm where drapes, furniture, or other objects
block the flow of air to the vents.

Battery installation and replacement

Note:
Place the control panel into sensor test mode prior to
replacing the batteries. If the control panel is not in sensor test
mode during battery replacement, an alarm/tamper condition
may be indicated.
To install or replace the batteries in this alarm:
1.
Slide the alarm body off of the mounting plate.
2.
If replacing batteries, remove the old batteries and
properly dispose of them as recommended by the battery
manufacturer.
3.
Install the new batteries. Note the polarity illustration in the
battery compartment (Figure 3).
Figure 3: Batteries
_
+
_
4.
Slide the alarm body back onto the mounting plate.
Note:
The mounting plate will not close if all three
batteries are not installed.
2
Battery compartment
Figure 4: Sliding the alarm on the mounting plate
5.
Perform a sensor/RF test with the control panel. See "RF
communication test" on page 3
When replacing the batteries, use one of the following
approved brands:
Duracell MN1500 or MX1500
Energizer E91
Note: For battery replacement information, see interlogix.com.
Use of a different battery may have a detrimental effect on the
alarm operation.
Note:
Constant exposures to high or low humidity may reduce
battery life.
After installing or changing the batteries, reinstall your alarm.
Test your alarm by using the Test/Hush button and check that
the green Power LED is on.

Mounting the alarm

Note:
Verify RF performance prior to permanently mounting
the alarm. See "RF communication test" on page 3.
The CO alarm can be wall mounted or ceiling mounted.
To mount the alarm:
1.
Slide the alarm body off of the mounting plate. Place the
mounting plate in the desired location, and mark the
location of the two mounting holes. Orient the mounting
plate vertically or horizontally as shown in the following
figures.
Note:
The alarm can also be directly mounted to a single
gang box.
Figure 5: Vertical mounting
Mounting latch
600-6520-95 Carbon Monoxide Alarm Manual
Alarm mounting guide
Alarm mounting guide
Mounting hole
Warning
XXXXxx XXX x xxx
XX XXX XXXXxxx
XXXX XXX XXXxx
XXXXXXX X XX xx
XXXXxx XXX x xx
XX XXX XXXX xx
XXXX XXX XXXxx
Alarm
XXXXXXX X XX xx
XXXXxx XXX xxx
procedure
XX XXX XXXXxx
XXXX XXX XXXx
XXXXXXX X XX
label
XXXXxx XXX xxx
XX XXX XXXX xx
XXXX XXX X X
XXXXXXX X XXxx
xxxxxxxxxxx
XXXXxxx
xxxxxxxxxxx
Mounting hole

Advertisement

Table of Contents
loading

Table of Contents