Extension Cord Recommendations - Lincoln Electric COMMANDER SVM153-A Service Manual

Lincoln electric welding system user manual
Table of Contents

Advertisement

B-12
TABLE B.4 – COMMANDER 500 SIMULTANEOUS WELDING AND POWER LOADS
Welding
Output Range
Setting
30-575
500
350
250
150
90
* Each duplex receptacle is limited to 20 amps.
** Not to exceed 50 A per 120 VAC branch circuit when splitting the 240 VAC output.
EXTENSION CORD
RECOMMENDATIONS
An extension cord can be used with the auxiliary power
outputs as long as it is of ample size. Table B.5 lists
permissible extension cord lengths based on conduc-
tor size and auxiliary power output.
TABLE B.5 – COMMANDER 500 EXTENSION CORD LENGTH RECOMMENDATIONS
Current
Voltage
Load
(Amps)
(Volts)
(Watts)
15
120
1800
30
15
240
3600
60
20
120
2400
20
240
48010
25
240
6000
30
240
7200
38
240
9000
50
240
12000
OPERATION
Permissible
Power - Watts
(Unity Power
Welding Output
500A/40V
500A/40V
350A/30V
250A/29V
150A/27V
90A/25V
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
(9)
40
(12)
(18)
75
(23)
30
(9)
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
COMMANDER 500
Factor)
@ 120 V ± 10%*
0
0
9500
80*
12000
100**
12000
100**
12000
100**
10 AWG
8 AWG
75
(23)
125
(38)
150
(46)
225
(69)
50
(15)
88
(27)
100
(30)
175
(53)
90
(27)
150
(46)
75
(23)
120
(37)
100
(30)
Permissible Auxiliary
Current in Amperes
@ 240 V ± 10%*
0
0
0
0
40
50
50
50
6 AWG
4 AWG
175
(53)
300
350
(107)
600
138
(42)
225
275
(84)
450
225
(69)
250
175
(53)
300
150
(46)
250
125
(38)
200
B-12
(91)
(183)
(69)
(137)
(76)
(91)
(76)
(61)