Extension Cord Length Recommendations - Lincoln Electric RANGER 275 Operator's Manual

Lincoln electric welder user manual
Hide thumbs Also See for RANGER 275:
Table of Contents

Advertisement

A-8
Current
Voltage
Load
(Amps)
(Volts)
(Watts)
15
120
1800
15
240
3600
20
240
4800
25
240
600
30
240
7200
38
240
9000
CONNECTION OF Ranger 275 TO PREMISES WIRING
POWER
240 Volt
60 Hz.
COMPANY
3-Wire
Service
METER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
Connection of Ranger 275 to premises wiring must be done by a licensed electrician and must comply
with the National Electrical Code and all other applicable electrical codes.
INSTALLATION
Table A.1

Extension Cord Length Recommendations

Maximum Allowable Cord Length in ft (m) for Conductor Size (AWG)
14 AWG
12 AWG
30
(9)
40
(12)
60
(18)
75
(23)
60
(18)
Figure A.1
240 VOLT
120 VOLT
120 VOLT
240 VOLT
WARNING
RANGER 275
10 AWG
8 AWG
75
(23)
125
(38)
150
(46)
225
(69)
100
(30)
175
(53)
90
(27)
150
(46)
75
(23)
120
(37)
100
(30)
GROUNDED CONDUCTOR
40 AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
GND
N
NOTE: No. 8 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
6 AWG
4 AWG
175
(53)
300
(91)
350
(107)
600
(183)
275
(84)
450
(137)
225
(69)
250
(76)
175
(53)
300
(91)
150
(46)
250
(76)
NEUTRAL
BUS
N
PREMISES
DISCONNECT AND
SERVICE
GROUND
OVERCURRENT
PROTECTION
SIZE RECOMMENDATIONS.
A-8