Superior DRT35STDMN Installation And Operation Instructions Manual page 21

Drt35 series see through and peninsula direct vent gas fireplaces
Table of Contents

Advertisement

Innovative Hearth Products
Superior
DRT35 See Through and Peninsula Direct Vent Gas Fireplace
TM
VERTICAL VENT FIGURES / TABLES (CONTINUED)
Table C
H
Maximum
H Maximum
+H
1
feet
(meter)
feet
(meter)
5
(1.524)
2
(0.610)
10
(3.048)
4
(1.219)
15
(4.572)
6
(1.829)
20
(6.096)
8
(2.438)
V + V 1 + H + H 1 = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
H + H 1 = 20 feet (6.096 meters) Max.
u
When using Secure Flex, use Firestop / Spacer SF4.5VF
v
When using Secure Flex, use Firestop / Spacer SF4.5HF
Example: If 20 feet total (H+H
then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H+H
maximum total horizontal run of 20 feet.
Figure 32 - Side Vent - THREE ELBOWS
Table D
H +
Maximum
H
1
feet
(meter)
5
(1.524)
5
(1.524)
10
(3.048)
15
(4.572)
20
(6.096)
H + H
= 20 feet (6.096 m) Max.
1
V + V
+ H + H
= 40 ft. (12.192 m) Max.
1
1
u
When using Secure Flex, use Firestop / Spacer SF4.5VF
v
When using Secure Flex, use Firestop / Spacer SF4.5HF
Example: If 20 feet total (H+H
) horizontal vent run is needed, then 4 feet minimum
1
of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical, you are allowed
5 feet of (H+H
) horizontal run up to a maximum total horizontal run of 20 feet.
1
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only
vertical component in the system. See Figure 38.
Figure 33- Top Vent - THREE ELBOWS
V Minimum
feet
(meter)
1
(0.305)
2
(0.610)
3
(0.914)
4
(1.219)
) horizontal vent run is needed,
1
) horizontal run up to a
1
V Minimum
feet
(meter)
Elbow Only
1
(0.305)
2
(0.610)
3
(0.914)
4
(1.219)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H1
u
Ceiling Firestop /
Spacer (SV4.5VF)
v
Wall Firestop/
Spacer (SV4.5HF)
V1
V
u
Ceiling
Firestop / Spacer
V 1
(SV4.5VF)
H 1
Installation and Operation Instructions
u
Ceiling Firestop /
Spacer (SV4.5VF)
H
v
Wall Firestop/
Spacer (SV4.5HF)
H
900300-00, 02/2015
V
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Drt35stdmpDrt35stdenDrt35pfdmnDrt35pfdmpDrt35pfden