C C Check Of R.v. Coil - Mitsubishi Electric MXZ-2A40VA Service Manual

Split-type, heat pump air conditioners outdoor unit
Hide thumbs Also See for MXZ-2A40VA:
Table of Contents

Advertisement

The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)

C C Check of R.V. coil

• When heating operation does not work.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning on the power supply, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 230V AC between pin1 and
pin 2 at connector CN912?
Yes
Turn off power supply of indoor and outdoor unit.
Disconnect the connector
CN912. Is there normal
resistance to R.V. coil?
Yes
Replace the 4-way valve.
• When cooling operation does not work.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning on the power supply, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 230V AC between pin1 and
pin 2 at connector CN912? W
Yes
1. Turn off power supply of the indoor and the outdoor unit, and
disconnect the connector CN933 or CN781.
2. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION in COOL mode.
Is there voltage 12V DC
between the connector CN933
pin 1 (+) and pin 3 (-) or the
connector CN781
pin 5 (+) and pin 3 (-) ?
Yes
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
No
No
Replace the R.V. coil.
No
W If the connector CN912 is not connected or R.V. coil is open, voltage
occurs between terminals even when the control is OFF.
No
Replace the power P.C.board or
the noise filter P.C. board.
MXZ-2A
CN912
Power P.C. board
CN781
CN933
Inverter P.C. board
1. Turn off power supply of indoor and outdoor unit, and
disconnect the connector CN933 or CN781.
2. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION in HEAT mode.
Is there voltage 12V DC
between the connector CN933
pin 1 (+) and pin 3 (-) or the
connector CN781
pin 5 (+) and pin 3 (-) ?
Yes
Replace the power P.C. board or
the noise filter P.C. board.
Replace the 4-way valve.
65
MXZ-3A/4A
Noise filter P.C. board
Outdoor electronic control
P.C. board
No
Replace the inverter P.C.
board or the electronic
control P.C. board.