Connecting Relay Modules

1. Mount either remotely or in the control panel.
2. Connect to control's keypad terminals using the
connector harness supplied with the module. Use
standard 4-conductor twisted cable for long wiring
runs.
If power supervision is required, use the Trigger
Module terminals as described in the Aux Power
Supervision Connections paragraph in the Wiring
to Keypads section (page 2-3).
3. Set each module's device address according to the
table at right.
4. Connect the desired field wiring to the unit's relay
contact terminals.
COVER TAMPER (REED) SWITCH
(4229 Module and 6164 Keypad is shown in the Expansion Zones sections on page 2-7)
4204
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
4-PIN TOUCHPAD PLUG
EITHER OR BOTH
CAN BE USED
TB1
13 14 15 16
Figure 11. 4204 Connections to Control
Mounting and Wiring the Control
Notes
• Use 4204/4229 modules or 6164 keypad.
• Supervision: 4204/4229 modules and 6164
keypad are supervised against removal. The
module's device address is displayed as follows if
a module is disconnected from the control's
terminals, or if the module cover is removed and
the tamper jumper is installed:
Alpha: CHECK xx Wire Expansion
FAULT xx Wire Expansion
TAMPER xx Wire Expansion
ALARM xx Wire Expansion
Fixed-Glass: lxx (or 91 if field *199 set for 2-digit
display)
where "xx is the module's address.
• If communication/tamper failure occurs on a
device with zones wired to it, all zones on the
device will be displayed in their respective
partitions.
Relay Module Addresses
4204/6164
Address 4229/6164
no. 1
12
no. 2
13
no. 3
14
no. 4
15
† Use these addresses if using only relays with the
6164 and not its zones.
†† Use these addresses if using zone expansion
and relays with the 6164; supports only the first
four zones in parenthesis.
††† Not available if zone doubling used.
RELAY
4
TYPICAL
(SHOWN "OFF")
RELAY
3
RELAY
2
RELAY
1
DATA IN
YEL
FROM CONTROL
BLK
(–) GROUND
GRN
DATA OUT
TO CONTROL
RED
(+) 12V
††
Address
†††
no. 1 (zn 09-16)
07
no. 2 (zn 17-24)
08
no. 3 (zn 25-32)
09
no. 4 (zn 33-40)
10
no. 5 (zn 41-48)
11
C
NC
NO
C
NC
NO
C
NC
NC
NO
C
NC
NO
TB2
4204_conn-1-V0
2-11