Annual Servicing; Removal Of Firefront; Removal Of Controls - Baxi Bermuda Inset 2 Boiler 50/4 Installation And Servicing Manual

Fireside gas central heating unit
Table of Contents

Advertisement

7.0
Annual Servicing - Page 19

7.1 Annual Servicing

1. To perform annual servicing of the back boiler it is
necessary to remove the firefront.
2. After servicing, complete the relevant section of the
"Benchmark" Installation, Commissioning and Service
Record Log Book. This should be in the possession of the
user.

7.2 Removal of Firefront

1. Isolate the electrical supply to the appliance.
2. Turn the gas service tap to the off position (Fig. 34).
3. Refer to the separate firefront instructions for the removal
of the firefront.

7.3 Removal of Controls

1. Turn the boiler thermostat to "O" position (Fig. 36).
2. Undo the retaining screw and remove the heat shield and
electrical plug from the socket (Fig. 35).
3. Disconnect the union at the gas service cock and remove
the fire feed pipe.
4. Remove the thermostat phial from the boiler (Fig. 38).
5. Lift and remove the injector insulation pad (Fig. 37).
6. Undo the nut on the sensing pipe at the adaptor.
7. Undo the four screws retaining the door and remove the
door (Fig. 38).
8. Undo the two screws retaining the controls to the
combustion box sides (Fig. 39).
9. Slacken the screw holding the controls to the combustion
box base tray.
10. Withdraw the controls from the boiler.
19